Oa/30/2002 08:11 FAI 212 333 8306 ATC 0004

Mr. Bernard P. Orlan September 27 2002 Indoor Air Quality Assessment Page 3 P. S. 6SQ________________ ATCPtoieotNo. 1.5-19125-0334

Relative Humidity

The relative humidity indoors ranged from 47.0 percent to 64.7 percent. Two (2) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from -46.3 to 59,9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 381 ppm to 1042 ppm. All of the indoor measurements were within the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 527 ppm. Therefore, tile maximum acceptable level of CO2 at this location was 1227 ppm (background level -1- 700 ppm). The highest reading (1042 ppm) was recorded in Room 129 approximately at 1:10 P.M. with 28 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide meafiurcments are used as an indicator of available outdoor air. The primary source of COj indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all readings.

OBSERVAITONS

During this assessment, ATC noted the following:

• The building was occupied at the time of the assessment; * No unusual odors were detected.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. All of the indoor temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by aSHRAE Standard 55-1992 during the mechanical cooling season (sumnieitime conditions). 2. Two (2) of the indoor measurements for relative humidity were above the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 3. All of the indoor CO? measurements were within the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level 4. Concentrations of CO were within applicable guidelines.

CITY_21MC1OO_OO3O1678O

NYC-WTC_000350649

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000350649Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →