Mr. Bernard p. Orlan September 25,2002
Indoor Air Quality Assessment Page 3
P. S- 65Q ATCProiCCtNo. 15-19125-0334
Relative Humidity
The relative humidity indoors ranged from 46.1 percent to 55.5 percent. All of the indoor
measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity measurements ranged from 46.3 to
53,1 percent
Carbon Dioxide ConGentratian
Carbon dioxide concentrations indoors ranged from 425 ppm to 945 ppm. All of the indoor
measurements were within the ASHRAE Standard 62-2001 recommended maximiun
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 632 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1332 ppm (background level ■+ 700 ppm). The highest reading (1005 ppm) was
recorded in Staircase E approximately at 1:20 P.M, with no occupants. Levels above the
recommended maximum do not indicate a health risk, Cwbc’i dioxide measurements are used as
an indicator of available outdoor ait. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentraliqn
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations
were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from Oppra TO 2 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No unusual odors were detected.
FINDINGS
Based on the real-time measurements, the following findings arc presented:
1- All of the indoor temperature measurements were below the range of 73 to 79'’F (at 50
percent relative humidity) as recommended by ASHRAF Standard 55-1992 during the
mechanical cooling season (summertime COndmonE).
2. All of the indoor measurements for relative humidity were within the ASHRaE
recommended range of 30 to 60 percent for occupant comfort.
3. All of the indoor CO2 measurements were within the ASHRAE Standard 62-2001
recommended maximum concentration of <700 ppm above the background level.
4. Concentrations of CO were within applicable guidelines.