09425/2002 08:27 FAI 212 353 8306 ATC ®003
Mr. Bernard P. Orlan September 25,2002
Indoor Air Quality Assessment Page 2
P. S. 65Q________________ ATC Project No, 15-19125-0334
EVALUATION CRITERIA
Currently, there are no regulatoty standards for indoor air quality in non-industrial buildings,
such as offices and schools. For tee real-time data collected, ATC uses tee commonly accepted
guidelines Cited in tee following publications;
Ventilation for Acceptable Indoor Air Quality (ASHAAE 62-2001), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal EnvironmeTital Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AHA).
Tabic 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all Of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLEI
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2)_________ above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO)__________ USEPA NPAAQS)
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter; 68-75‘F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
USEPA = United States Eavirojjnwiital Protection Agency
Real-Time environmental Meast'rememts
ATC collected one hundred and sixteen (116) sets of real time environmental measurements
consisting of one hundred and twelve (112) from inside the school building and four (4)
outdoors. All three floors of the school were surveyed, These results are described below. Field
data sheets arc found in Attachment 1. Readings began at approximately O8:00A-M.
Tempefaiure
Indoor dry bulb temperature measurements ranged from 64.5 to 73.2 “p. All of the indoor
temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity)
as recommended by ASHRAE Standard 55-1992 during tee mechanical cooling season
(summertime conditions). The outdoor temperature measurements ranged from 65.3 to 71,9 ®F.