Mr. Bernard I'. Orlan October 30, 2001
Indoor Air Quality Assessment Page 2
Manhattan Acad, of Technology @ P.S. 2M ATC Project No. 15-19125-0273
times. The information presented in this report should be used by the Board of Education as a
guide to asses,s the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications;
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLE 1
TARGET GLTDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
_____________ . _________________________
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2) above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited m
(CO) ASHRAE 62) ____________
Respirable 50 micrograms per cubic meter USEPA NPAAQS (as cited m
Particulates (PMiq) of air (pg/m3) - annual ASHRAE 62)
150 micrograms per cubic
meter of air (pg/m^) - 24 hour
Temperature Summer: 73-79°F at 50% RH ASHRAE55
Winter; 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary' Ambient-Air Quality Standard
SAMPLING RESULTS
Real-Time Environmental Measurements
ATC collected eleven (11) sets of real-time environmental measurements consisting of ten (10)
in the school building and one (1) outdoors. These results are shown in Table 2. Field data
sheets are found in Attachment 1.