Mr. Bernard P. Orlan February 28, 2002 Indoor Air Quality Assessment Page 2 P. S. 234M ATC ProjecT No. 15-19125-0279
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to as.sess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industnal buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED »ll&
Galbon Dioxide <700 parts per million (ppm) ASHRAE62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQ.S) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (|xg/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - recommendation for children/sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002878648
NYC-WTC_000382101
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000314875
IAQ measurements collected March 11, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314646
ATC indoor air quality measurements report for PS 234M (Feb 2002).
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314706
Indoor air quality measurements at PS 234M, Feb 11, 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314690
IAQ measurements report for PS 234M requested by BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199173
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on February 12, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000272216
Memo: IAQ measurements at P.S. 234M, school site, requested by NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314888
IAQ measurements collected March 7, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182883
Report of indoor air quality measurements collected at PS 234M on February 13, 2002, to assess acceptable air quality conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000272279
IAQ measurements conducted at P.S. 234M for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294387
Report of IAQ measurements at PS 234M for BOE program, dated March 7, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383700
Memo re: indoor air quality measurements at PS 89M, Feb 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000381366
Indoor air quality measurements at PS 234M; report to BOE, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397271
IAQ measurements report for PS 234M, Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397455
ATC IAQ measurements at PS234M, May 13–15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314771
Indoor air quality measurements collected March 26, 2002 at PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372203
ATC report detailing IAQ measurements at PS 234M, June 21, 2002, for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315123
Indoor air quality measurements collected May 6, 2002 for PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000314875
IAQ measurements collected March 11, 2002 at PS 234M for BOE.
Similar indexed content
NYC-WTC_000314646
ATC indoor air quality measurements report for PS 234M (Feb 2002).
Similar indexed content
NYC-WTC_000314706
Indoor air quality measurements at PS 234M, Feb 11, 2002, per BOE request.
Similar indexed content
NYC-WTC_000314690
IAQ measurements report for PS 234M requested by BOE.
Similar indexed content
NYC-WTC_000199173
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on February 12, 2002.
Similar indexed content