Mr. Bernard I*. Orlan October 30, 2001
Indoor Air Quality Assessment Page 3
Manhattan Acad, of Technology @ P.S. 2M ATC ProiectNo. 15-19125-0273
TABLE 2
REAL-TIME MEASUREMENTS
Location Temperature Carbon Carbon Respirable
w Dio.vide .Particulates
’.. .... ,1
___________________ __________
Staircase 4 & 5 76.8 71.6 1240 2 103
Office 301 ■ 76.9 70.5 1275 2 67
Hallway outside room 77.3 69.5 1043 1 80
303
Room 303 77.8 69.0 1290 1 97
Room 306 77.8 68.1 935 1 72
Room 305 77.8 66.0 946 2 66
Room 308 77.9 62.1 1764 2 62
Room 309 78.4 68. r 1423 1 74
Staircase / Exit 6 78.8 68.9 948 1 110
Room 318 79.2 69.3 1120 1 112
Outdoors 77.8 64.1 506 1 86
Temperature
Indoor dry bulb temperature measurements ranged from 76.8 °F to 79.2 °F. All measurements
were above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAF
Standard 55-1992 during the heating season (wintertime condihons). The outdoor temperature
was 77.8°F.
Relative Humidity
The relative humidity indoors ranged from 62.1 percent to 71.6 percent. All of the indoor
measurements were above the ASHRAE’s recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity was 64.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 935 ppm to 1764 ppm. Six (6) CO2
measurements were above the ASHRAF Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 410 ppm. Therefore, the acceptable level of CO2 at this location was 1,110
ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a
health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The
primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1-2 ppm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.