Indoor air quality assessment, High School of Economics and Finance

Machine-extracted title · confidence 42%

ATC Associates indoor air quality assessment report for H.S. of Economics and Finance (Feb 2000).

NYC-WTC_000359576–000359580
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 21,2000 Indoor Air Quality Assessment Page 3 High School of Economics and Finance ATC Project No. 15-19125-0035

TABLE 2 DIRECT-READING MEASUREMENTS

Location Military Temperature Relative Carbon Carbon Time Humidity Dioxide Monoxide (%) (ppm) (ppm)

Room 704 8:26 67.7 30.8 532 0 Room 703 8:30 70.6 31.1 780 0 Room 304 8:38 72.4 28.2 617 0 Room 407 8:52 74.7 29.1 994 0 Room 510 8:58 75.8 27.2 842 1 Room 608 9:02 7^ 28.6 To 1 Outside Air (By 9:15 46.2 20.7 494 o Main Entrance) Room 704 13:45 71.7 38.1 1,444 0 Room 703 13:47 73.9 34.2 1.260 0 Room 608 13:50 74.8 34.3 1,245 0 Room 605 13:53 76.0 30.2 1,060 0 Room 510 l3?58 7^ 304 17157 0 Room 407 14:02 77.1 29.4 1,110 0 Room 304 14:05 77.3 28.2 1,075 0 Out,side Air (By 14:10 65.3 22.1 548 9 Main Entrance)

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 532 ppm to 1.444 ppm. Eight (8) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of 1,000 ppm. Carbon dioxide measurements are used as an indicator of available outdoor air. Levels above 1,000 ppm do not indicate a heaitn risk. The primary source of CO2 indoors is occupant respiration. The outdoor CO2 concentration was 494 ppm at 9:1 5 M.T. and was 548 ppm at 14:10 M.T.

Carbon Monoxide Concentration

Eleven (11) of the carbon monoxide concentrations indoors were 0 ppm. Two (2) of the concentrations indoors were 1 ppm. These concentrations were below the NAAQS of 9 ppm. The outdoor CO concentrations were 2 ppm at 9:15 M.T. and 14:10 M.T.

Temperature

Indoor dry bulb temperature measurements ranged from 67.7°F to 77.3°F. Four (4) of the measurements were s'ighdy above the range of 69 to 76°F at 30 percent relative humidity recommended by ASIIRAE Standard 55-1992 during the mechanical heating season

W\ 19Q9'ihbaq\reports\boe'US[i&f'

CITY_21MC100_013440481

NYC-WTC_000359578

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359578Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402524

Indoor air quality measurements collected March 19, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000219378

ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.

Similar indexed content

NYC-WTC_000179980

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.

Similar indexed content

Compare copies and versions →