Indoor air quality report, High School M894, Jun 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements collected June 13, 2002 for the referenced school.

NYC-WTC_000291996–000291999
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 14, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

Real-Time Environmental Measurements

.A.TC collected one hundred and forty (140)' sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 71.3 to 80.5 °F. Eighteen (18) of the mdoor measurements for temperature were below and one (1) of the measurements was above the range of 73 to79 "F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 74.9 to 76.0 °F.

Relative Humidity

The relative humidity indoors ranged from 42.5 percent to 51.2 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 46.9 to 50.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 557 ppm to 1296 ppm. Six (6) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 500 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1200 ppm (background level + 700 ppm). The highest reading was recorded in room 805 at around 1:10PM with 28 occupants. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 28 pg/m^ with an average 9 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 35 pg/m^ to 82 pg/m^ wiffi an average of 67 pg/m3.

CITY_21MC100_003079784

NYC-WTC_000291998

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000291998Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000410927

Indoor air quality report for H.S. for Leadership & [name], June 2002.

Similar indexed content

NYC-WTC_000291723

Indoor air quality measurements report for HS Leadership & [name], May 2002.

Similar indexed content

NYC-WTC_000335273

Indoor air quality report for High School for Leadership & M894; June 13, 2002.

Similar indexed content

NYC-WTC_000399222

Indoor air quality measurements at the High School for Leadership & [name]; May 2002.

Similar indexed content

Compare copies and versions →