Indoor air quality assessment, High School of Economics and Finance

Machine-extracted title · confidence 42%

ATC Associates indoor air quality assessment report for H.S. of Economics and Finance (Feb 2000).

NYC-WTC_000359576–000359580
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 21, 2000 Indoor Air Quality Assessment Page 4 I ligh School of Economics and Finance ATC Project No. 15-19125-0035

wintertime conditions. One (1) of the measurements was slightly below the recommended range. The outdoor temperature was 46.2°F at 9:15 M.T. and was 65.3°F at 14:10 M.'l’.

R^hdjyeHumidity

The relative humidity indoors ranged from 27.2 percent to 38.1 percent. Six (6) of the indoor measurements were below ASHRAE's recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 20.7 percent at 9:15 A.M. and was 22.1 percent at 14:10 M.T.

FINDINGS

Based on the inspection of the occupied spaces and direct-reading, the following findings are presented:

1. Concentrations of CO were within existing applicable standards and guidelines. 2. Five (5) of the thirteen (13) measurements of temperature were above e.xisting applicable standards and guidelines. 3. Six ( 6) of the thirteen (13) measurements of relative humidity were below existing applicable standards and guidelines. 4. Eight (8) of the thirteen (13) measurements of CO? were above existing applicable standards and guidelines.

CONCLUSION

The high levels of CO, indicate that insufficient fresh air is being brought into the building. Two rooms (#407 and #608) had high levels (994 ppm & 1088 ppm) before 9:00 A.M. Room #704 had 532 ppm at 08:26 and 1444 ppm (the highest measuic '; 13:45. Temperatures in rooms on the S''*, 4'\ 5'*’ and 6'*’ floors had all risen to higher than optimal levels by early afternoon. This indicates problems with temperature control in the building. Indoor temperatures should remain constant over time if the system is operating properly.

RECOMMENDATIONS

Based on the measurements made during this assessment^ ATC recommends the following:

Operation of the HVAC controls should be thoroughly checked and the entire system should be balanced; Ensure that any perimeter heating or duct pre-heat systems are properly controlled; Dampers should be checked to make sure that they are in the proper position: The percentage of fresh air in the ventilation stream should be increased to maintain CO, levels below 1,000 ppm throughout the day.

W\1999 ih-iaq\report5\hoe>HSE&F

CITY_21MC100_013440482

NYC-WTC_000359579

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359579Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402524

Indoor air quality measurements collected March 19, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000219378

ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.

Similar indexed content

NYC-WTC_000179980

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.

Similar indexed content

Compare copies and versions →