NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

IAQ report, PS 89M, Mar 2002

Machine-extracted title · confidence 32%

ATC IAQ measurements at PS 89M, March 14, 2002, per BOE.

NYC-WTC_000326825–000326829
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 15, 2002 Indoor Air Quality Assessment : . 3 'Pages ; P. S. 89M' ATC Project No. 15-19125-0297

Real-Time Environmentat. Measurements

ATG collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.6 °F to 77 °F. Thirty-three (33) of the indoor measurements for temperature were above and thirty-seven (37) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55- 1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 51.8 to 55.3 °F.

Relative Humidity

The relative humidity indoors ranged from 28.9 to 38.4 percent. Four (4) of the indoor measurements for relative humidity were below and seventy-six (76) were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 37.6 to 44.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 468 ppm to 1242 ppm. Seventy-eight (78) of the CO? indoor measurements were below and two (2) were above the ASHRAE Standard 62- 1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO? concentration was 435 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1135 ppm (background level + 700 ppm). The highest reading (1242 ppm) was taken in room 408 at 10:00 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.

Respirable Particulates TPM2 s)

Respirable particulate concentrations* indoors ranged between 24 pg/m^ to 56 pg/m?. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMp s concentration for the entire school building was approximately 41 pg/m^.

CITY_21MC1OO_OO539O45O

NYC-WTC_000326827

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000326827Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →