Mr. Bernard P. Orlan February 6, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Pub. Service (M894') ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and thirty-nine (139) sets of real-time environmental measurements consisting of one hundred and thirty-three (133) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:20 P.M. The results are described below;
Temperature
Indoor dry bulb temperature measurements ranged from 63.8°F to 73.8°F. Thirty (32) of the . measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the pt, 5th , 5th 9th igth , nth 12^*^ , 13^^ and 14th floors. The outdoor temperature range was 35.1°F to 40.4°F.
Relative Humidity
The relative humidity indoors ranged from 17.6 percent to 33.1 percent. All but three of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity.range was 17.6 and 33.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 415 ppm to 1282 ppm. - Three (3) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background, level. The outdoor (background) CO2 concentrations ranged from 412 ppm to 511 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1211 ppm (background level + 700 ppm). The highest reading was recorded in Room 1105, occupied by 27 people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0-2 ppm.
Respirable Particulates (PM2_j)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 34 pg/. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average outdoor respirable particulate concentrations ranged from 34 pg/m^ to 59 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002871641
NYC-WTC_000376917
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335364
ATC IAQ measurements collected February 8, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377102
Memobrief/letter reporting IAQ measurements at a NYC high school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215187
Report summarizing indoor air quality measurements collected at a high school location in late February 2002 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370422
Indoor air quality measurements collected March 6, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335452
ATC IAQ measurements collected February 15, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335512
Indoor air quality measurements performed at the referenced high school per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000376933
IAQ report correspondence from ATC to NYC BOE for M894.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335327
ATC reports IAQ measurements collected February 5–6, 2002 for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000377122
Memo reporting indoor air quality measurements at a school site.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335364
ATC IAQ measurements collected February 8, 2002 for the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335382
ATC IAQ measurements collected February 11, 2002 for the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
Similar indexed content
NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
Similar indexed content
ATC IAQ measurements collected February 8, 2002 for the referenced school.
Similar indexed content
NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similar indexed content
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
Similar indexed content