Mr. Bernard P. Orlan February 28, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Pub. Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty-one (141) sets of real-time environmental measurements consisting of one hundred and thirty-six (136) in the school building and five (5) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:17 A.M. and concluded after 1:43 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 66.8°F to 74.9°F. Ten (10) were below the range of 68 to 7 5 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 41.7°Fto54.5°F.
Relative Humidity
The relative humidity indoors ranged from 29 percent to 30.8 percent. 24 readings were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 28.6 to 40 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 375 ppm to 1064 ppm. None of the measurerhents were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged from 332 ppm to 599 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1108 ppm (background level + 700 ppm). The highest reading was recorded in Room 515 at around 1:03 P.M. Levels above the recommended maximum do not- indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2-4 ppm.
Respirable Particulates (PM2_j)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 37 ug/m^ with an average 9 ug/m^- None of the measurernents were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged fi’om 51 pg/m^ to 95 pg/m^ with an average of 66 ug/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_000464452 NYC-WTC_000377124
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370422
Indoor air quality measurements collected March 6, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335550
Indoor air quality measurements collected at the referenced school.
15 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215187
Report summarizing indoor air quality measurements collected at a high school location in late February 2002 to assess environmental conditions.
15 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377102
Memobrief/letter reporting IAQ measurements at a NYC high school.
15 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370411
ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335364
ATC IAQ measurements collected February 8, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259914
IAQ field report with conditions and scope of work, Mar 6, 2002
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370407
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370389
ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.
Similar indexed content
NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
Similar indexed content
Indoor air quality measurements collected March 6, 2002 at the referenced school.
Similar indexed content
Indoor air quality measurements collected at the referenced school.
Similar indexed content
NYC-WTC_000215187
Report summarizing indoor air quality measurements collected at a high school location in late February 2002 to assess environmental conditions.
Similar indexed content