NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 26, 2002
Indoor Air Quality Assessment Page 3'
H.S. for Leadership & Pub. Service .(M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and thirty-four (134) in the school building and six (6) outdoors. The
basement of the school was not surveyed because it was not accessible to the public. Field data .
sheets are found in the Attachment. Readings began at 8:25 A.M. and concluded after 1:45 P.M.
The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 68.3°F to 73.4°F. All of the
measurements were within the range of 68 to 75°F' (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature range was 59.8°F to 61.5°F.
Relative Humidity
The relative humidity indoors ranged from 27.6 percent to 35.2 percent. Fifty-five (55)
measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity range was 28.3 to 29.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 550 ppm to 1156 ppm. All of the
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations ranged from 480 ppm to 491 ppm. Therefore, the maximum acceptable level of
CO2 at this location was 1191 ppm (background level + 700 ppm). The highest reading was
recorded in Room 1205 at around 12:00 P.M. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concemraiion
Carbon monoxide concentrations indoors were 1-2 ppm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2-3 ppm.
Respirable Particulates (PM2, s)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 23 pg/m^ with an
average 9 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
The outdoor respirable particulate concentrations ranged from 53 pg/m^ to 63 pg/m^ with an
average of 58 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.