NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Board of Education IAQ report letter

Machine-extracted title · confidence 44%

Correspondence reporting indoor air quality measurements at a NYC school.

NYC-WTC_000377084–000377087
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 26, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Pub. Service (M894) ATC Project No. 15-19125-0290

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of respirable particulates, CO , CO2 and TVOCs, were within applicable standards and guidelines. 2. All temperature measurements were within the range of 68 to 75 °F (at 50 percent relative humidity recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Fifty-five (55) of the relative humidity measurements were below the ASHRAE .recommended range of 30 to 60 percent for occupant comfort.

.It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261or212.

Sincerely, A TC ASSOCIA T£S INC. Reviewed by:

v^Zfiannis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002871890

NYC-WTC_000377087

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000377087Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335364

ATC IAQ measurements collected February 8, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000335512

Indoor air quality measurements performed at the referenced high school per BOE request.

Similar indexed content

Compare copies and versions →