Mr. Bernard P. Orlan February 26, 2002
Indoor Air Quality Assessment Page 4
H.S. for Leadership & Pub. Service ('M894) ATC Project No. 15-19125-0290
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration w'as also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO , CO2 and TVOCs, were within applicable
standards and guidelines.
2. All temperature measurements were within the range of 68 to 75°F (at 50 percent relative
humidity recommended by ASHRAF Standard 55-1992 during the heating season
(wintertime conditions).
3. Fifty-five (55) of the relative humidity measurements were below the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
.It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
1-
'—Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division