Mr. Bernard P. Orlan March 13,2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

.^TC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.

field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at approximately 1:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.5 "F to 77.3 °F. Nineteen (19) of the indoor measurements for temperature was above and eleven (11) were within the range of 68 to 75®F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 46.1 to 48.9 °F.

Relative Humidity

Tlie relative humidity indoors ranged from 26.5 to 37.4 percent. Nineteen (19 of the indoor ineasurements for relative humidity were below and eleven (11) were v/ithm the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 33 to 36.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 455 ppm to 680 ppm. All of the CO? measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (backgi’ound) CO2 concentration was 393 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1093 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concenlration

Carbon monoxide concentrations were 0 ppm for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all outdoor readings.

Respirable Particulales (PM2,3)

Respirable particulate concentrations* indoors ranged betw'een 26 pg/m^ to 36 pg/m^. None of the measurements were above the NTAAQS of 65 pg/m^ 24-hour average concentration of paniculate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 33 pg/m^. The PM2 5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC100_002954290

NYC-WTC_000289452

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000289452Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →