Mr. Bernard P. Orlan October 30, 2001 Indoor Air Quality Assessment Paged Manhattan Acad, of Technology @ P.S. 2M ATC Project No. 15-19125-0273

Respirable Particulates

Respirable particulate concentrations indoors ranged between 62 pg/m^ and 112 ug/m^. All measurements were above the NPAAQS/ASHRAE guideline of 50 p.g/m3 (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter) but below the NPAAQS/ASHRAE guideline of 150 pg/m^ (24-hour average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration was 86 pg/m3. The high outdoor level is the major factor in the elevated indoor levels.

OBSERVATIONS

During this assessment, ATC noted the following:

• The exhaust system was operating during the assessment; • The air conditioning was running in Room 301; • Windows were open in Rooms 305 and 309.

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented;

1. Measurements of temperature, relative humidity in all locations examined were above applicable standards and guidelines.

2. Measurements of CO and respirable particulates were within acceptable ranges.

3. Six out of ten CO2 measurements were above the range recommended by ASHRAE 62- 1999.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. However, the temperature and relative humidity may be uncomfortable for some occupants. The supply of outdoor air to the classrooms should be increased.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep CO? levels below the recommended maximum by increasing the level of outdoor air; • Perform an assessment of the entire building to compare the 3’’d floor, where Manhattan Academy of Technology is located, with the rest of the P.S. 2M building; • Keep a log of all complaints and illnesses to better target problem areas and times;

CITY_21MC1OO__OO32 7415O

NYC-WTC_000329952

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000329952Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →