Mr. Bernard P. Orlan May 6, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
respirable particulate concentration measurements ranged from 42 to 46 pg/m^ with an average
of 45 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-bour average.
1V0C Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Sixty-two (62) of the indoor measurements for temperature were below the range of 73 to
79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992
during the summer season. ,
3. Thirty-eight (38) of the indoor measurements for relative humidity were below and thirty-
two (32) were within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort.
4. Ten (10) of the indoor measurements for COg were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading (1416 ppm) was taken in room 404 at 9:54 AM with 31 occupants. Levels
above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outside makeup air. The primary source
of CO2 indoors is occupant respiration. The school building was occupied during ATC’s
assessment.
5. All of the indoor measurements were below the NPAAQS of 65 ug/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
5
CITY_21MC100_003271929
NYC-WTC_000328330