Mr. Bernard P. Orlan May 6, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M ATC Project No. 15-19125-0297
REAL-TIME Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were surveyed. These results are described below..
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11 ;30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 73.8 °F. Sixty-two (62) of
the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent
relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer
season . The outdoor temperature measurements ranged from 60.7°F to 60.9°F.
Relative Humidity
The relative humidity indoors ranged from 24.8 to 32.2 percent. Thirty-eight (38) of the indoor
measurements for relative humidity were below and thirty-two (32) were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity
measurements ranged from 31.6 to 31.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 471 ppm to 1416 ppm. Ten (10) of the
indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The maximum outdoor
(background) COp concentration was 473 ppm. Therefore, the maximum acceptable level of
CO2 at this location was 1173 ppm (background level + 700 ppm). The highest reading (1416
ppm) was taken in room 404 at 9:54 AM with 31 occupants. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor GO concentration were
also 1 ppm for all collected readings.
Respirable Particulates (PM2.5) s
Respirable particulate concentrations* indoors ranged between 14 jug/m^ to 20 pg/m^. The
average PM2.5 concentration for the entire school building was approximately 17 g/m3. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor