Mr. Bernard P. Orlan May 6, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 73.8 °F. Sixty-two (62) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 60.7°F to 60.9°F.
Relative Humidity
The relative humidity indoors ranged from 24.8 to 32.2 percent. Thirty-eight (38) of the indoor measurements for relative humidity were below and thirty-two (32) were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 31.6 to 31.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 471 ppm to 1416 ppm. Ten (10) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 473 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1173 ppm (background level + 700 ppm). The highest reading (1416 ppm) was taken in room 404 at 9:54 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were also 1 ppm for all collected readings.
Respirable Particulates (PM2,j)
Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 20 pg/m^. The average PM2.5 concentration for the entire school building was approximately 17 g/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
C11X_21MC1OO_OO286421O
NYC-WTC_000369725
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000369752
IAQ measurements collected at PS 89M for BOE evaluation, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392778
ATC indoor air quality measurements collected May 3, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392803
ATC indoor air quality report for P.S. 89M submitted to BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199010
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392718
ATC report of IAQ measurements collected at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369706
ATC report of IAQ measurements at PS 89M, May 2002, for BOE evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000220651
Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394501
Indoor air quality measurements collected April 29, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392661
IAQ report dated April 22, 2002 for PS 89M; BOE evaluation requested.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392743
ATC IAQ measurements conducted at P.S. 89M for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328327
ATC reports IAQ measurements at PS 89M, 201 Warren St., for May 2002 per BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369752
IAQ measurements collected at PS 89M for BOE evaluation, May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392803
ATC indoor air quality report for P.S. 89M submitted to BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313624
ATC IAQ measurements at P.S. 89M for May 9, 2002, BOE evaluation.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000369752
IAQ measurements collected at PS 89M for BOE evaluation, May 2002.
Similar indexed content
NYC-WTC_000392778
ATC indoor air quality measurements collected May 3, 2002 for BOE.
Similar indexed content
NYC-WTC_000392803
ATC indoor air quality report for P.S. 89M submitted to BOE.
Similar indexed content
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 8, 2002.
Similar indexed content
NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similar indexed content