NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 22, 2002
Indoor Air Quality Assessment Page 3
P. S.89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11:300 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.9 °F to 77.2 °F. Sixteen (16) of the
indoor measurements for temperature were below and fifty-four (54) were within the range of 73
to 79®F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992
during the summer season . The outdoor temperature measurements ranged from 70 °F to
72.3°F.
Relative Humidity
The relative humidity indoors ranged from 46.5 to 55.1 percent. All of the indoor measurements
for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 51.4 to 53.2
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 576 ppm to 1432 ppm. Four (4) of the
indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The maximum outdoor
(background) CO2 concentration was 530 ppm. Therefore, the maximum acceptable level of
CO2 at this location was 1230 ppm (background level + 700 ppm). The highest concentration
was detected in room # 402 (1432 ppm) at 10:00 AM with 32 occupants. Levels above the
recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as
an indicator of available outside makeup air. The primary source of CO2 indoors is occupant
respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged between 2 ppm to 3 ppm for all readings.
These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentration was 3 ppm for all collected readings.
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 20 pg/m3 to 51 ug-inC The
average PM2.5 concentration for the entire school building was approximately 40 g/m^. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter. Thirty-two (32) of the