Mr. Bernard P. Orlan April 22, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
severity (70) instantaneous indoor measurements were above USEPA recommended
concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable
particulate concentration measurements ranged from 58 to 122 pg/m^ with an average of 89
pg/rn^. Nine (9) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All
of the outdoor instantaneous readings were above the USEPA recommended concentration of 40
pg/m3 for sensitive individuals and children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
7VOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Sixteen (16) of the indoor measurements for temperature were below and fifty-four (54)
were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the
ASHRAE Standard 55-1992 during the summer season .
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. Four (4) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest concentration was detected in room # 402 (1432 ppm) at 10:00 AM with 32
occupants. Levels above the recommended maximum do not indicate a health risk. Carbon
dioxide measurements are used as an indicator of available outside makeup air. The primary
source of CO2 indoors is occupant respiration.
5. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Thirty-
two (32) of the seventy (70) instantaneous indoor measurements were above USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. Nine (9) of
the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of
the outdoor instantaneous readings were above the USEPA recommended concentration of
40 pg/m3 for sensitive individuals and children.