Mr. Bernard P. Orlan March 15, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297 Fort>'-three (43) of the seventy (70) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable parl;iculate concentration measurements ranged from 97 to 106 pg/m^ with an average of 102 pg/m-*. All outdoor measurements were above the NPAAC)S of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the EPA recommended guideline for children and sensitive individuals of 40 pg/m^-

* The measurements made during this assessment were instantaneous readings, the NPyVAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Thirty-three (33) of the indoor measurements for temperature were above and thirty-seven (37) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Four (4) of the indoor measurements for relative humidity were below and seventy-six (76) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Seventy-eight (78) of the CO2 indoor measurements were below and two (2) were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1242 ppm) was taken in room 408 at 10:00 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m-* 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Forty-three (43) of the seventy (70) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. All outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the EPA recommended guideline for children and sensitive individuals of 40 pg/m^-

CITY_21MC100_0 03047471

NYC-WTC_000313342

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313342Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →