Mr. Bernard P. Orlan March 15, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Enatronmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temuerature

Indoor dry bulb temperature measurements ranged from 71.6 °F to 77 °F. Thirty-three (33) of the indoor measurements for temperature were above and thirty-seven (37) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55- 1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 51.8 to 55.3 °F.

Relative Humidity

The relative humidity indoors ranged from 28.9 to 38.4 percent. Four (4) of the indoor measurements for relative humidity were below and seventy-six (76) "w ere within the ASHRAF- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 37.6 to 44.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 468 ppm to 1242 ppm. Seventy-eight (78) of the CO2 indoor measurements were below and two (2) were above the ASHRAF Standard 62- 1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 435 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1135 ppm (background level + 700 ppm). The highest reading (1242 ppm) was taken in room 408 at 10:00 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 24 pg/m^ to 56 pg/m^. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 41 pg/m^.

CITY_21MC100_0 03047470

NYC-WTC_000313341

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313341Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →