Mr. Bernard P. Orlan October 30, 2001 Indoor Air Quality Assessment Page 4 Manhattan Acad, of Technology @, P.S. 2M ATC Project No. 15-19125-0273
Respirable Particulates
Respirable particulate concentrations indoors ranged between 62 pg/m^ and 112 pg/m^. All measurements were above the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter) but below the NPAAQS/ASHRAE guideline of 150 pg/m^ (24-hour average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration was 86 pg/mA The high outdoor level is the major factor in the elevated indoor levels.
OBSERVATIONS
During this assessment, ATC noted the following:
• The exhaust system was operating during the assessment; • The air conditioning was running in Room 301; • Windows were open in Rooms 305 and 309.
FITTINGS
Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:
1. Measurements of temperature, relative humidity in all locations examined were above applicable standards and guidelines.
2. Measuiements of CO and respirable particulates were within acceptable ranges.
3. Six out often CO2 measurements were above the range recommended by ASHRAE 62- 1999.
CONCLUSION
Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. However, the temperature and relative humidity may be uncomfortable for some occupants. Tlie supply of outdoor air to the classrooms should be increased.
RECOMMENDATIONS
Based on the findings and conclusions above, ATC recommends the following:
• Reep CO2 levels below the recommended maximum by increasing the level of outdoor air; • Perform an assessment of the entire building to compare the S^d floor, where Manhattan Academy of Technology is located, with the rest of the P.S. 2M building; • Keep a log of all complaints and illnesses to better target problem areas and times;
CITY_21MC100_011274465
NYC-WTC_000200220
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
8 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗7 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177847
Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.
8 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗6 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.982 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177982
Letter reporting indoor air quality measurements collected at P.S. 150M on May 16, 2002.
Similarity score 0.981 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.981 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.979 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content