Memo presenting IAQ measurements for PS 65Q at 103-22 99th St.

NYC-WTC_000350416–000350419
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

05/24/2002 13:07 FAI 212 353 8306 ATC 121038

Mr. Bernard P. Orlan May 24.2002 Indoor Air Quality AsEcssmsiit Pages F. S. 650 ATC Project No. 15-19125-0334

EVATJJATIQN CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Qualify (ASHRAE 62-2001), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Oceupaney (ASHRAE S5-1992); Industrial Hygienists Guide to rndoor Air Qtialify Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values docs not assure that acceptable indoor air quality will be achieved at all times.

TABLEI TARGET GUIDELINES FOR INPOOR AIR QUALITY PARAMETERS EVALUATED Hi

Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO?) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from ^CO)__________ USEPA NPAAQS) Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE55 USE?A United States Environmental Protection Agency

Real-Time EwvmorsEna:rAL Measukements

ATC collected eighty (SO) sets of real-time environmental measurements consisting of seventy- eight (78) from msidc the school building and two (2) outdoors. All tliree floors of the school were surveyed. These results arc described below. Field data Sheet? are found in Attachment 1. Readings began at 9:55 A.M. and concluded after 1:26 P.M.

Teinu^ralute

Indoor dry bulb temperature measurements ranged from 70.5 “F to 76.4 °F. Forty-six (46) measurements were below and tluTty-two (32) were within the range 0173 to 79'’F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the mCeh^iMcal cooling season (summertime conditions). The outdoor temperature measurement were 70.5’F and 77,3°F.

CITY_21MC100_003016440

NYC-WTC_000350417

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000350417Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →