May 24, 2002
Mr. Bernard P, Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza Nortli
Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment
P.S. 65Q
103-22 99th Street
Ozone Park, New York 11417
ATC Project No. 1549125-0334
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ)
measurements; collected on May 21, 2002, at the referenced school. The New York City Board
of Education (BOE) requested these measurements as part of a program to determine if
acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (CO.) and carbon mOilOXide (CO) with a Q-Trak® Model 8551, manufactured by
TSI, Tnc.
Mr. Prasad Doddapaneni, Environmental Technician of ATC’s New York City office, conducted
the assessment.
ATC’s findings are based on a visual inspection, real-time environmental measurements and
conditions present in the school at the time of tlx- assessment
The assessment was perfomaed consistent with generally accepted indoor air quality assessment
practices. As with all such assessments, there were inherent limiUtiOfts created by constraints of
time, operational and work practice variability, variations in indoor air quality parameters and
sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times. The information presented in this report should be
used by the BOE as a guide to assess tire need for further improvements in current indoor air*
quality control activities.