Mr. Bernard P, Orlan 24,2002
Indoor Air Quality Assessment
P^.65Q^____________
Relative ffumidity
The relative humidity indoors ranged from 27.6 percent to 37.9 percent. Sixteen (16) of the
indoor measurements were below and sixty-two (62) were within the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort. The outdoor relative humidity were 27 and 46.5
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged frcttn 541 ppm to 1203 ppm All of the indoor
measurements were below the ASHRAE Standard 62-2001 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 535 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1235 ppm (background level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Caibon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO? indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monOXide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/aSHRAE guideline of 9 ppm. The outdoor CO concentration were 1
ppm for all readings.
OBSERVATIONS
During this assessment, ATC noted tlic following:
• The building was occupied at the time of the assessment.
• Kitchen door to outside yard is open.
FINDESGS
Based on the real-time raeasmcmcnti, tire following findings are presented;
1. Concentrations of CO2 and CO were within applicable standards and guidelines.
2. Forty-six (46) measurements were below and thirty-two (32) were within the range of 73 W
79*F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992
during the mechanical cooling Season (summertime conditions).
3. Sixteen (16) of the indoor measurements for relative humidity were below and sixty-two (62)
were within tile AbHRAE recommended range of 30 to 60 percent for occupant comfort.
CITY_21MC1OO_OO3O16441
NYC-WTC_000350418