Mr. Bernard P, Orlan October 15, 2001 Indoor Air Qualib,’ Assessment Page 4 Manhattan Acad, of Technology (d), P.S. 2M ATC Project No. 15-19125-0273
Relative Humidity
The relative humidity indoors ranged from 33.4 percent to 54.7 percent. All of the indoor measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 45.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 580 ppm to 3,054 ppm. Six (6) CO7 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 426 ppm. Therefore, the acceptable level of CO2 at this location was 1,126 ppm (background level + 700 ppm). Two rooms (Rooms 307 & 308) had CO2 levels that were between 1.8 and 2.7 times greater than the recommended maximum. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 to 10 ppm. Six (6) of the indoor readings were at 50% or more of the NPAAQS/ASHRAE guideline of 9 ppm. One reading (Staircase Exit 4 & 5) was 10 ppm. The outdoor CO concentration was 2 ppm.
Respirable Particulates
Respirable particulate concentrations indoors ranged between 29 pg/m^ and 84 pg/m^, Twelve (12) of the sixteen (16) indoor measurements were above the NPAAQS/ASHRAE guideline of 50 pg/m3 (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration was 98 pg/m3. The high outdoor level is the major factor in the elevated indoor levels.
TVOC Conceniration
TVOC concentrations indoors were 0 ppm for all readings. The AIHA guideline for non industrial buildings is 1 ppm. The outdoor TVOC concentration was 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • An elevated CO level (10 ppm) was recorded in Staircase Exit 4 & 5; • The custodian of P.S. 2M reported that all of the building’s boilers were off; • The exhaust system was operating during the assessment; • There was a smell of food throughout the floor, the kitchen for P.S. 2M is in the basement of the building; • The air conditioning was running in Room 311 and Room 301; • Windows were open in Rooms 303, 304, 306, 307, 309, 318, 320 and the Boys Toilet; • Windows were closed in Room 305 and no students were in the room;
CITY_21MC100_003274171
NYC-WTC_000329973
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000324128
ATC indoor air quality assessment report for PS 2M school building.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329949
LIAQ report for IAQ assessment at P.S. 2M / NYC DOE.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000200217
Cover letter and report summary from ATC Associates regarding an indoor air quality assessment conducted at P.S. 2M in October 2001.
9 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328266
Indoor air quality measurements collected at the referenced school for BOE.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
10 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311687
Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328327
ATC reports IAQ measurements at PS 89M, 201 Warren St., for May 2002 per BOE request.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313339
ATC IAQ memo detailing measurements and scope of work at PS 89M.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199010
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 8, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000324128
ATC indoor air quality assessment report for PS 2M school building.
Similar indexed content
NYC-WTC_000329949
LIAQ report for IAQ assessment at P.S. 2M / NYC DOE.
Similar indexed content
NYC-WTC_000200217
Cover letter and report summary from ATC Associates regarding an indoor air quality assessment conducted at P.S. 2M in October 2001.
Similar indexed content
NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similar indexed content
NYC-WTC_000328266
Indoor air quality measurements collected at the referenced school for BOE.
Similar indexed content