NYC 9/11 Public Portal Document

Mr. Bernard P, Orlan October 15, 2001 Indoor Air Qualib,’ Assessment Page 4 Manhattan Acad, of Technology (d), P.S. 2M ATC Project No. 15-19125-0273

Relative Humidity

The relative humidity indoors ranged from 33.4 percent to 54.7 percent. All of the indoor measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 45.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 580 ppm to 3,054 ppm. Six (6) CO7 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 426 ppm. Therefore, the acceptable level of CO2 at this location was 1,126 ppm (background level + 700 ppm). Two rooms (Rooms 307 & 308) had CO2 levels that were between 1.8 and 2.7 times greater than the recommended maximum. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 2 to 10 ppm. Six (6) of the indoor readings were at 50% or more of the NPAAQS/ASHRAE guideline of 9 ppm. One reading (Staircase Exit 4 & 5) was 10 ppm. The outdoor CO concentration was 2 ppm.

Respirable Particulates

Respirable particulate concentrations indoors ranged between 29 pg/m^ and 84 pg/m^, Twelve (12) of the sixteen (16) indoor measurements were above the NPAAQS/ASHRAE guideline of 50 pg/m3 (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration was 98 pg/m3. The high outdoor level is the major factor in the elevated indoor levels.

TVOC Conceniration

TVOC concentrations indoors were 0 ppm for all readings. The AIHA guideline for non­ industrial buildings is 1 ppm. The outdoor TVOC concentration was 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • An elevated CO level (10 ppm) was recorded in Staircase Exit 4 & 5; • The custodian of P.S. 2M reported that all of the building’s boilers were off; • The exhaust system was operating during the assessment; • There was a smell of food throughout the floor, the kitchen for P.S. 2M is in the basement of the building; • The air conditioning was running in Room 311 and Room 301; • Windows were open in Rooms 303, 304, 306, 307, 309, 318, 320 and the Boys Toilet; • Windows were closed in Room 305 and no students were in the room;

CITY_21MC100_003274171

NYC-WTC_000329973

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000329973Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →