10/03/2002 07:44 FAI 212 353 8306 ATC @1010

Mr. Bernard P. Orlan October 3 2002 Indoor Air Quality Assessment Page 2 P. S. 65Q________ —■ - ATC Project Ho. 15-19125-0314

EVALUATION CRITERIA

Cpirently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASHR4S 62-2001), American Society of Heating, Refrigerating, add Air-Conditioning Engineers (ASHRAE); TJiermal Environmental Conditionsfor Human Occupancy (ASHRAE 5S-19P2); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (ATHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be athioved at all times. TABLEI TARGET GUIDELINES FOR EsDOOR AIR QUALITY PARAMETERS EVALUATED

Carbon Dioxide <700 parts per million (ppm) ASHRAE62 (CO2)_________ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75’F at 50% RH Relative Humidity 30-60% ASHEAE55 USEPA = United States Environmental Protection Ascney

Real-Time Environmental Measumments

ATC collected one hundred and sixteen (116) sets of real-time environmental measurements consisting of one hundred and twelve (112) from inside the school building and four (4) outdoors. All three floors of the school were surveyed- Tlieie results are described below. Field data sheets found in Attachment 1. Readings began at approximately 08:00AM.

T&nt>eratur^

Indoor dry bulb temperature raeaSUfeiBents ranged from 69.9 to 78.2“F. Eighty-three (83) of the indoor temperature measurements were below the range of 73 to 79®F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature measurements ranged from 72,0 to 7S.9 ’F.

CITY_21MC100_003016673

NYC-WTC_000350570

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000350570Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →