NYC 9/11 Public Portal Document Oe/30/2002 08:19 FAS 212 353 8306 ATC @022
Mi. Bernard P. Oflan September 30 2002 Indoor Air Quality Assessment Page 2 _____ ATCFroiectNo. 15-19125-0334
evaluation CMTERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC USCS the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-2001), American Society Of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); thermal Environmental Conditionsfor Human Occupanty (ASHRAE SS-19512); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values docs not assure that acceptable indoor air quality will be achieved at all times. TABLEI TARGET GUIDELINES FOR INDOOR AIR QTJALITV PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2)_________ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Temperature Summer: 73-79T at 50% RH ASHRAE 55 Winter; 68-75“F at 50% RH Relative Humidity 30-60% ASHRAE 55 USEPA = United States Environmcnial Protection Agency
Real-Time ErmRowMEWTAL Measurements
ATC collected one hundred and sixteen (116) sets of real-tinie environmental meaBurements consisting of one hundred and twelve (112) from inside the school building and four (4) outdoors. All three floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at approximately 08:00A,M.
T^mfi&rahire.
Indoor dry bulb temperature measurements ranged from 66.6 to 73.8°F. Ninety-nine (99) of the indoor tempetature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRaE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature measurements ranged from 67.9 to 72.4 °F.
CITY_21MC1OO_OO4O35963
NYC-WTC_000207835
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
5 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
5 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177847
Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.
5 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗5 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
Similar indexed content