Mr. Bernard P. Orlan October 15, 2001 Indoor Air Quality Assessment Page 5 Manhattan Acad. ofTechnolo^v i® P.S. 2M ATC ProiectNo. 15-19125-027,3

• Windows and the door were closed m Room 308 and the room was fully occupied, this is the room with the highest COg level (3,054 ppm);

nNDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations of CO? and respirable particulates in multiple locations were above applicable standards and guidelines.

2. Measurements of CO, relative humidity and TVOCs were within acceptable ranges.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. However, the supply of outdoor air to the classrooms should be increased.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep CO? levels below the recommended maximum by increasing the level of outdoor air; • Perform an assessment of the entire building to determine the source of the elevated CO detected in the staircases and the hallway; • Keep a log of all complaints and illnesses to better target problem areas and times; • Conduct timely follow-up monitoring/inspection to ensure that recommendations were effective.

It is our pleasure to provide these indoor air consultative services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 212 or 261,

Yours truly. A TC ASSOCIA TES INC.

A

■lames R. Colm, CIH. CSP Regional Manager Industrial Hygiene Division

Atlachments

CITY_21MC1OO_OO3267168

NYC-WTC_000324132

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000324132Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311687

Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →