Mr. Bernard P. Orlan October 15, 2001 Indoor Air Quality Assessment Page 3 Manhattan Acad, of Technolosv (SrP.S. 2M ATC Project No. 15-19125-0273

SAMPLING RESULTS

Real-Time Environmental Measurements

ATC collected seventeen (17) sets of real-time en vironmental measurements consisting of sixteen (16) in the school building and one (1) outdoors. These results are shown in Table 2. Field data sheets are found in Attachment 1.

TABLE 2 REAL-TIME MEASUREMENTS Loeation Temperature Relative Carbon ■ rvo< ■■li Humidity zoz Dint.de Monoxide (n.-) ippn.) Illi Hill■s IPPm) aiRi Room 311 70.9 44.9 825 3 48 0 Room 320 74.2 54.7 880 3 68 0 Room 318 76.4 50.5 620 62 0 Staircase Exit 6 77.1 47.9 618 66 0 Boy'S ’ Toilet 77.6 4^ 668 3 53 0 3™ fir hallway outside girls 78.0 47.5 650 6 70 0 toilet Office 309 78.0 45.9 715 4 58 0 Room 307 78.1 TTO 2102 J 54 0 Room 308 77.6 33.4 3054 “T 29 0 Room 305 78.9 43.5 580 2 0 Room 306 78.9 1154 2 84 0 Room 303 78.5 41.9 1196 4 82 0 Staircase Exit 4 75.9 44.5 702 MO 79 0 and 5 Office 301 ~j 75.9 46.1 1060 5 49 0 Toilet in Office 78.1 51.2 1401 57 0 301 Room 304 77.6 47.3 1288 5 65 0 Outdoors 68.5 45.3 426 2 98 0

Temveraiure

Indoor dry bulb temperature measurements ranged from 70.9 °F to 78.9 °F. All but two of the measurements were above the ranee of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature was 68.5°F.

CITY_21MC100_003267166

NYC-WTC_000324130

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000324130Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311687

Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →