NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan November 9, 2001 Indoor .Air Quality .Assessment Page 3 StuvAesant Hiuh School (.M477l ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and sixteen (116) sets of real-time enx'ironmental measurements consisting of one hundred and fourteen (1 14) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 1:30 P.M.
Teinperatiire
Indoor dry bulb temperature measurements ranged from 70.7 °F to 78.3 °F. Sixty-six (66) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 50.1 to 58.9 °F.
Jielative
The relative humidity indoors ranged from 17.2 percent to 31.9 percent. Only four (4) measurements were within the ASHRAE-rscommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 17.5 and 28.0 percent.
Carbon DioxidcCpncentratim
Carbon dioxide concentrations indoors ranged from 509 ppm to 1994 ppm. Thirteen (13) CO? measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COy concentrations were 450 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1150 ppm (background level -1- 700 ppm). The highest reading, 1994 ppm, was in Room 735. Rooms with COa levels above the recommended maximum were found on the 1st, 3rd, 4th, 5^'“', 7tl'' 8th an ci IQth floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COo indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0— 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.
Respirable Particnlaies (PAdT,
Respirable particulate concentrations indoors ranged between 9 pig/m^ to 28 pig/m^. .All of the measurements were below the NPAAQS of 65 jug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 26 and 30 pig/m-’.
CITY_21MC100_0 03045892
NYC-WTC_000197566
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182478
Cover letter and report summary for indoor air quality measurements conducted at a New York City Board of Education school in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182879
Report of indoor air quality measurements collected at PS 234M on February 11, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182883
Report of indoor air quality measurements collected at PS 234M on February 13, 2002, to assess acceptable air quality conditions.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177942
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
Similar indexed content
Similar indexed content