NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Pages P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 4:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.7 °F to 78.7 °F. Seventeen (17) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 44.2 to 49.0 °F.

Relative Humidity

The relative humidity indoors ranged from 27.0 percent to 32.8 percent. Twenty-eight (28) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 60.1 to 80.3 percent.

Carbon Dioxide Concentration

Carbon dioyide concentrations indoors ranged from 488 ppm to 897 ppm. All of the measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 473 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1173 ppm (background level -1- 700 ppm). The highest measurement was recorded in room 118. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm to 1 ppm.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 38 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 23 pg/m-\ This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 56 to 63 pg/m3 with an average of 59 pg/m^.

CITY_21MC100_003083646

NYC-WTC_000189108

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000189108Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, PS 234M, Jan 2002

NYC-WTC_000177858

Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 29, 2002, to evaluate building contamination.

Similar indexed content

Compare copies and versions →