NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 14, 2002
Indoor Air Quality Assessment Pages
P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one
(51) from inside the school building and nine (9) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after
4:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.7 °F to 78.7 °F. Seventeen (17)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature measurements ranged from 44.2 to 49.0 °F.
Relative Humidity
The relative humidity indoors ranged from 27.0 percent to 32.8 percent. Twenty-eight (28) of
the measurements were below the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity ranged from 60.1 to 80.3 percent.
Carbon Dioxide Concentration
Carbon dioyide concentrations indoors ranged from 488 ppm to 897 ppm. All of the
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 473 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1173 ppm (background level -1- 700 ppm). The highest measurement was recorded
in room 118. Levels above the recommended maximum do not indicate a health risk. Carbon
dioxide measurements are used as an indicator of available outdoor air. The primary source of
CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0
ppm to 1 ppm.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 38 pg/m^. All
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 23 pg/m-\ This average
concentration was below the USEPA recommended concentration for sensitive individuals such
as asthmatic people and children. The outdoor respirable particulate concentration ranged from
56 to 63 pg/m3 with an average of 59 pg/m^.
CITY_21MC100_003083646
NYC-WTC_000189108
OCR can misread numbers and units. Confirm readings against the page image before using them.