Mr. Bernard P. Orlan November 9. 200 1 Indoor Air Qualily .Assessment Page 4 Stuvvesant High School ( M477') .ATC Project No. 15-19125-0246
Fillers with a higher efflcienc} rating were installed on the HVAC units that serve rooms on the 3''d. 411'’. 6th and floors (See Attachment 1). The PMg 5 concentration range for those rooms was 9 - 27 pg/m-’ with an average of approximately 14 pg/nH. The PMo.s concentration range for the other rooms was 10-28 pg/m-’ with an average of approximately 14 pg/m^. The average PMo 5 concentration for the entire school building was approximately 14 pg/m^.
7'1'OC Concentraticn
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment. ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • Windows were open in Rooms 231,233, 339, 501, 1004.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.
2. Fifteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.
3. Sixb)'-six (66) temperature measurements were above the range recommended by ASHRAE 55-1992.
4. All but four relative humidity measurements were below the range recommended by ASHRAE 55-1992.
CONCLUSION
Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC's investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO? levels indicate the need for increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on the 3rd, 4th, 6th and 7th foots did not significantly reduce respirable particulate levels compared to the other rooms.
RECOMMENDATIONS
Based on the findings and conclusions above. ATC recommends the following:
CITY_21MC100_003045893
NYC-WTC_000197567
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182478
Cover letter and report summary for indoor air quality measurements conducted at a New York City Board of Education school in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
Similar indexed content
Similar indexed content