Mr. Bernard P. Orlan October 12, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant H.S. (M477) ATC Project No. 15-19125-0246
SAMPLING RESULTS
Real-Time Environmental Measurements
ATC collected ninety-six (96) sets of real-time environmental measurements consisting of ninety-four (94) in the school building and two (2) outdoors. These results are described below. Field data sheets are found in Attachment 1.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to 80.3 °F. Forty-two measurements (44%) were above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These readings were on the 6^^, 7th, gth, 9th and lOth floors. The outdoor temperature range was 69.0to71.4°F.
Relative Humidity
The relative humidity indoors ranged from 48.3 percent to 61.9 percent. The 61.9% level was in Room 305, all other measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 51.2 to 59.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 449 ppm to 1830 ppm. Fourteen (14) CO2 measurements were at or above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 365 ppm. Therefore, the acceptable level of CO2 at this location was 1065 ppm (background level ■+• 700 ppm). Rooms with high CO2 levels were found on all floors except the 9^^ floor. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 - 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 - 2 ppm.
Respirable Particulates
Respirable particulate concentrations indoors ranged between 18 pg/m^ and 43 pg/m^. All concentrations were below the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration range was 33 to 42 pg/m^.
CITY_21MC100_003081564
NYC-WTC_000188513
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
13 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182879
Report of indoor air quality measurements collected at PS 234M on February 11, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182899
Report of indoor air quality measurements collected at PS 234M on February 25, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
NYC-WTC_000182669
Transmittal letter accompanying an indoor air quality assessment report for a Department of Education school conducted in October 2001.
Similar indexed content