Lab report, indoor air quality, 4 Wall Street, 2001

Machine-extracted title · confidence 40%

Final indoor air quality evaluation report for 4 Wall Street, Oct 2001.

NYC-WTC_000417388–000417408
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document rttHfcSO'

Oct-05-2JI3I 11:04 From-CLAYTONGGROUPCl + T-S24 P.OOr/021 F-2E1 ^daytoii C « oTjTVcV“r''‘*

27 to 36 The detection limit of the pDR instrument used to measure the respirable particulate concentrations was 1 pg/m<

ASHR.AE Standard 62-1999 recommends that levels of total paniculate m outdoor air entering a building not exceed the USEPA's National Ambient Air Quality Standards (NAAQS) of 75 pay 11!" Air containing higher levels of paniculate must be filtered to bring particulate levels within the guidelines, ASHRAE Standard 62-1999 (Addendum lo Ventiiaiion for Acceptable bjdoorAir Quality) recommends that, in accordance with the Clean Air Act of 1987 (i.e„ USEPA's NAAQS), levels of respirable paniculate (particles of less chan !0 microns aerodynamic diameter) not exceed 50 pg/m'^ in outdoor air entering a building.

All of the indoor airborne respirable particulate concentrations measured were less than 50pg/in'\

Carbon Dioxide

Carbon dioxide concentrations measured by Clayton indoors in the building ranged from 420 to 6S0 pans per million of air (ppm). The outdoor carbon dioxide concentration ranged from 410 to 450 ppm over the 3-day evaluation. The accuracy of the direct-reading insirurrteni u,sed by Clayton is ± 50 ppm.

ASHRAE Standard 62-1999 recommends indoor carbon dioxide concentration of not more than 700 pptn above the outdoor carbon dioxide concentration. Based upon the outdoor levels measured over the 3 day evaluation, ite recommended upper limit for indoor carbon dioxide concentrations within the building would be calculated as approxinwieiy 1,110 to 1,150 ppm. As such, the interior carbon dioxide concentrations mea,suredby Clayton were Uss than the ASHRAE Standard 62-1999 upper limit, thereby Suggesting an adequate supply of outdoor air to the building.

Carbon dioxide is a product of human respiration and a surrogate for various occupant-generated indoor contaminants, Carbon dioxide does not present a health hazard at [he,se relatively low levels: however, concentrations which exceed the ASHRAE Standard 62-1999 upper limit generally are indicative of insufficient outdoor air ventilation ('ie,. outdooi air Huws below 15 cubic feel per minute [cfm] per occupant). The OS HA PEL for carbon dioxide exposure is 5.000 ppm as an S-hour time-weighted -average (TWA).

Carbon Monoxide

Carbon monoxide was not detected above i ppm at any of the indoor measurement location.*. Likewise, carbon monoxide was consisientfy measured at I ppm at the Watt Street outdoor sampling location. The accuracy of the direct-reading instrument used by C J ay ton is +3 ppm

3

04298 CITY_21MC100_008877508

NYC-WTC_000417393

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000417393Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000390450

Appendix A shows direct-reading environmental measurements; file references city project codes.

Similar indexed content

NYC-WTC_000390456

Appendix B lists analytical results for area air sampling of airborne fiber concentrations.

Similar indexed content

Compare copies and versions →