Mr. Bernard P. Orlan • April 15,2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATCProiectNo. 15-19125-0297 respirable particulate concentration measurements ranged from 46 to 50 pg/m^ with an average of 36 pg/m3. All of the outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the ten (10) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TI^OC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented;
1.. Concentrations of CO2, CO and TVOCs were below the applicable standards and guidelines. 2. Ten (10) of the indoor measurements for temperature were below, and sixty (60) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. All of the indoor measurements for relative humidity were within the ASHICVE- recommended range of 30 to 60 percent for occupant comfort. 4. One (1) of the indoor measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 485 ppm. Therefore, the maximum acceptable level of COp at this location was 1185 ppm (background level + 700 ppm). The highest reading was taken in room 506 at 9:00 AM with 23 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment. 5. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m- for sensitive individuals and children. All of the outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the ten (10) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
CITY_21MC100_003271733
NYC-WTC_000328269
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392743
ATC IAQ measurements conducted at P.S. 89M for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313556
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392778
ATC indoor air quality measurements collected May 3, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000222482
ATC Associates letter submitting indoor air quality measurement results collected on April 17, 2002, at P.S. 89M for the NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392661
IAQ report dated April 22, 2002 for PS 89M; BOE evaluation requested.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369723
ATC IAQ measurements at PS 89M for BOE, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313458
IAQ measurements at P.S. 89M; BOE evaluation, April 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369706
ATC report of IAQ measurements at PS 89M, May 2002, for BOE evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392620
ATC IAQ measurements report dated April 12, 2002 for PS 89M; BOE evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000220651
Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000394408
Report of IAQ measurements at P.S. 89M in April 2002, per BOE request.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313458
IAQ measurements at P.S. 89M; BOE evaluation, April 12, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392620
ATC IAQ measurements report dated April 12, 2002 for PS 89M; BOE evaluation.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400218
IAQ measurements at PS 89M for NYC BOE evaluation, March 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328293
ATC IAQ measurements collected at the referenced school for BOE.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392778
ATC indoor air quality measurements collected May 3, 2002 for BOE.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000392768
ATC report of IAQ measurements collected May 3, 2002 at the school.
Similar indexed content
NYC-WTC_000392743
ATC IAQ measurements conducted at P.S. 89M for NYC BOE.
Similar indexed content
NYC-WTC_000313556
Indoor air quality measurements collected at PS 89M for BOE.
Similar indexed content
NYC-WTC_000392778
ATC indoor air quality measurements collected May 3, 2002 for BOE.
Similar indexed content
NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
Similar indexed content