NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 15, 2002 Indoor Air Quality Assessment Page 3 P. S. 891M ATC Protect No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 64.5 °F to 73,1 °F. Ten (10) of the indoor measurements for temperature were below, and sixty (60) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by, the ASHRAE Standard 5.5-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 47.6 to 49.5 °F.

Relative Humidity

The relative humidity indoors ranged from 30.7 to 39.8 percent. Al! of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 47.1 to 51 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 539508 ppm to 1230 ppm. One (1) of the indoor measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 485 ppm. Therefore, the maximum acceptable level of COt at this location was 1185 ppm (background level -1- 700 ppm). The highest reading was taken in room 506 at 9:00 AM,with 23 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.

Respirable Particulates (PM^^ 5)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 40 pg/m^. The average PM2.5 concentration for the entire school building was approximately 25 pg/m^ . All of the indoor measurerhents were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor

CITY_21MC100_003271732

NYC-WTC_000328268

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000328268Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →