Indoor air quality measurements, HS Leadership, Mar 2002

Machine-extracted title · confidence 38%

ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.

NYC-WTC_000260028–000260032
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 21, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service fM894) ATC Project No. 15-19125-0290

Real-Time Ewikoxmemal Measurements ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:43 A.M. and concluded after 6:33 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 70.2 °F to 77.3 °F. Seventy-five (75) indoor measurement for temperature were above and fifty-three (53) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 43.6 °F to 45.3 °F.

Relative Humia'ity

The relative humidity indoors ranged from 29.1 percent to 40.1 percent. Tliree (3) of the indoor measurements for relative humidity were below and one hundred-twenty-five(125) were within the ASHRAE-reccmmended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 51.6 to 55.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 491 ppm to 1364 ppm. One of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration v/as 472 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1172 ppm (background level + 700 ppm). The highest reading (1364 ppm) was measured in room 506 at 12:48 PM with 34 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. ITie primary source of CO2 indoors is occupant respiration.

Carbo7t Mon oxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. The.se concentrations were below the NP.AAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm- 4 ppm.

Respirable Particulates (PM2,§)

Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 24 pg/m^ with an average 5 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate concentrations ranged from 18 pg m^ to 43 pgZm^ with an average of 30 pg/m^. All of the outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of

CONFIDENTIAL, CITY_21MC100_003463733 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260030

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260030Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

NYC-WTC_000370505

Indoor air quality measurements collected March 15, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000370496

Indoor air quality measurements collected March 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000259941

IAQ measurements collected Mar 11, 2002 for BOE

Similar indexed content

Compare copies and versions →