Mr. Bernard P. Orlan March 21, 2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Service fM894) ATC Project No. 15-19125-0290
Real-Time Ewikoxmemal Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings began at 10:43 A.M. and concluded after 6:33 P.M. The results are
described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.2 °F to 77.3 °F. Seventy-five (75)
indoor measurement for temperature were above and fifty-three (53) measurements were within
the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard
55-1992 during the heating season (wintertime conditions). The outdoor temperature range was
43.6 °F to 45.3 °F.
Relative Humia'ity
The relative humidity indoors ranged from 29.1 percent to 40.1 percent. Tliree (3) of the indoor
measurements for relative humidity were below and one hundred-twenty-five(125) were within
the ASHRAE-reccmmended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity range was 51.6 to 55.7 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 491 ppm to 1364 ppm. One of the indoor
measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration v/as 472 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1172 ppm (background level + 700 ppm). The highest reading (1364 ppm) was measured in
room 506 at 12:48 PM with 34 occupants. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. ITie primary source of CO2 indoors is occupant respiration.
Carbo7t Mon oxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. The.se concentrations
were below the NP.AAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from 2 ppm- 4 ppm.
Respirable Particulates (PM2,§)
Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 24 pg/m^ with an
average 5 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration for sensitive individuals
such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate
concentrations ranged from 18 pg m^ to 43 pgZm^ with an average of 30 pg/m^. All of the
outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of