Mr. Bernard P. Orlan March 13, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadershin & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school .building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:07 A.M. and concluded after 3:33 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 64.6 °F to 77.2 °F. Two (2) indoor measurement for temperature were below, fifty-one (51) measurements were above, and seventy- five (75) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 51.4 °F to 56.2 °F.
Relative Humidity
The relative humidity indoors ranged from 25.4 percent to 38.4 percent. One hundred and one (101) measurements for relative humidity were below and twenty-seven (27) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 33.4 to 49.7 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 422 ppm to 1312 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 694 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1394 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm 2 ppm. These concentrations were below the NPAAQS/ASHRAF guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm-4 ppm.
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 72 pg/m^ with an average 18 pg/m^- One (1) of the indoor measurement was above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred twenty-eight (128) instantaneous indoor readings were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate concentrations ranged from 56 pg/m3 to 112 pg/m3 with an average of 81 pg/m^. Nine (9) outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the outdoor instantaneous measurements were above the
CITY_21MC1OO_OO2865751
NYC-WTC_000370494
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394752
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370501
Indoor air quality measurements collected March 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259937
IAQ measurements collected Mar 8, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260092
ATC IAQ report for 90 Trinity Place, measurements collected April 11, 2002, BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219855
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396411
IAQ measurements performed at a NYC high school; report for BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394813
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000259960
IAQ measurements collected Mar 12, 2002 for BOE
Similar indexed content
NYC-WTC_000296816
ATC IAQ measurements report for 90 Trinity Place, Apr 23, 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
NYC-WTC_000260136
ATC IAQ measurements collected April 23, 2002 at the referenced school for BOE.
Similar indexed content
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similar indexed content