Indoor air quality report, 90 Trinity Place, 2002

Machine-extracted title · confidence 42%

IAQ measurements collected Mar 12, 2002 for BOE

NYC-WTC_000259960–000259963
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 13, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:07 A.M. and concluded after 3:33 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 64.6 °F to 77.2 °F. Two (2) indoor measurement for temperature were below, fifty-one (51) measurements were above, and seventy- five (75) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 51.4 °F to 56.2 °F.

Relative Humidity

The relative humidity' indoors ranged from 25.4 percent to 38.4 percent. One hundred and one (101) measurements for relative humidity were below and twenty-seven (27) measurements were within the ASHR/iE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 33.4 to 49.7 percent.

CarbonDio.xide Concentration

Carbon dioxide concentrations indoors ranged from 422 ppm to 1312 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 694 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1394 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. Tlie primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm-4 ppm.

Respirable Particulates ('PM2 5)

Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 72 pg/m^ with an average 18 pg/m3. One (1) of the indoor measurement was above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred twenty-eight (128) instantaneous indoor readings were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate concentrations ranged from 56 pg/m^ to 112 pg/m3 with an average of 81 pg/m^. Nine (9) outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the outdoor instantaneous measurements were above the

CONFIDENTIAL, CITY_21MC100_0 03463625 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259962

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259962Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370492

Indoor air quality measurements collected March 12, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000394813

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000259937

IAQ measurements collected Mar 8, 2002 for BOE

Similar indexed content

Compare copies and versions →