Mr. Bernard P. Orlan March 21, 2002
Indoor Air Quality Assessment Page 4
U.S, for Leadership & Public Service (M894) ATC Proiect No. 15-19125-0290
particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the twelve (12)
instantaneous outdoor readings was above the USEPA recommended concentration for sensitive
individuals such as asthmatic people and children of 40 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below
the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0
ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Seventy-five (75) indoor measurement for temperature were above and fifty-three (53)
measurements were within the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime
conditions).
3. Three (3) of the indoor measurements for relative humidity were below and one hundred-
twenty-fiive:(125) were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort.
4. One of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999
recommended :maximum concentration of <700 ppm above the background level The highest
reading (1364 ppm) was measured in room 506 at 12:48 PM with 34 occupants. Levels
above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outdoor air. The primary source of CO2
indoors is occupant respiration.
5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEPA recommended concentration for sensitive individuals such as asthmatic
people and children of 40 pg/m^. All of the outdoor measurements were below the NPAAQS
of 65 pg/m 3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter. One (1) of the twelve (12) instantaneous outdoor readings was above
the USEPA recommended concentration for sensitive individuals such as asthmatic people
and children of 40 pg/m^.