Mr. Bernard P. Orlan March 12, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service ('M894) ATC Project No. 15-19125-0290 micrometers or less in aerodynamic diameter. All of the outdoor instantaneous measurements were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour averag:e.
TVOC Concenif-ation
The TVOCs concentrauons were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.
OBSERX ATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Five (5) indoor temperature measurement were below, five (5) measurements were above, and one hundred eighteen (118) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wi:atertime conditions). 3. One hundred and twenty-three (123) indoor measurements for relative humidity were below and five (5) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occ:upant comfort. 4. One hundred twenty-six (126) indoor measurements for CO2 were below and two (2) were above the .ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 724 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1424 ppm (background level + 700 ppm). The highest indoor measurements was taken in room 506 at 12:19 PM with 27 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour averageconcentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^.
CONFIDENTIAL, CITY_21MC100_003463607 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259944
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259977
IAQ measurements collected Mar 13, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260033
ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259999
IAQ field report for March 15, 2002 measurements
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370534
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260060
ATC IAQ measurements at the referenced school, March 27, 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260018
IAQ measurements collected Mar 18, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370492
Indoor air quality measurements collected March 12, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000370473
March 11, 2002 IAQ measurements report for the BOE school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259999
IAQ field report for March 15, 2002 measurements
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370529
Indoor air quality measurements collected March 21, 2002 at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394729
Indoor air quality report for High School for Leadership & [name], Apr 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected March 15, 2002 at the referenced school.
Similar indexed content
Indoor air quality measurements collected March 13, 2002 at the referenced school.
Similar indexed content
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
Similar indexed content
IAQ measurements collected Mar 13, 2002 for BOE
Similar indexed content
NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
Similar indexed content