Indoor air quality report, High School for Leadership, 2002

Machine-extracted title · confidence 42%

IAQ measurements collected Mar 11, 2002 for BOE

NYC-WTC_000259941–000259945
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 12, 2002 Indoor Air Qualit)’ Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:40 A.M. and concluded after 3:50 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 62.9 °F to 76.1 °F. Five (5) indoor measurement were below, five (5) measurements were above, and one hundred eighteen (118) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by .ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 39.9 °F to 43.3 °F.

Relative Humidity

The relative humidity indoors ranged from 17.6 percent to 31.6 percent. One hundred and twenty-three (123) measurements were below and five (5) measurements were within the ASHRAF-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 33.4 to 49.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 426 ppm to 1835 ppm. One hundred twenty- six (126) indoor measurements for CO2 were below and two (2) were above the ASHRAE Sfcmdard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 724 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1424 ppm (background level + 700 ppm). The highest indoor measurements was taken in room 506 at 12:19 PM with 27 occupants. Levels above the reccmirended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Afonoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm 2 ppm. These concentrations were below the NPAAClS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 3 ppm-4 ppm.

Respirable Particulates (PM2,§)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 25 pg/m^ with an average 10 pg/ m^ None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and fie USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate concentrations ranged from 56 pg/m^ to 104 pg/m3 with an average of 79 pg/m^. Eight (8) outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5

CONFIDENTIAL, CITY_21MC100_003463606 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259943

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259943Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370505

Indoor air quality measurements collected March 15, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000370496

Indoor air quality measurements collected March 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

NYC-WTC_000259977

IAQ measurements collected Mar 13, 2002 for BOE

Similar indexed content

Compare copies and versions →