Multi-building sampling report, 14 Wall Street, Oct 2001

Machine-extracted title · confidence 35%

Clayton group report for sampling at the Multi-Building site, 14 Wall Street.

NYC-WTC_000390443–000390449
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Oct-05-2001 11:04 Fron-CLAVIONGGROUPQ + T-B24 P.007/021 F-261

^Clayton

27 to 36 (4g/m\ The detection limit of the pDR instrument used to measure the respirable paniculate concentrations was 1 pg/m\

ASHRAE Standard 62-1999 recommendLs that levels of total particulate in outdoor air entering a building not exceed the USEPA's National Ambient Air Quality Standards (NAAQS) of 75 pg/m’. Air containing higher levels of particulate must be filtered to bring paniculate levels within the guidelines. ASHRAE Standard 62-1999 [Addendum to VentUation for Acceptable Indoor Air Quality) recommends that, tn accordance with the Clean Air Act of 1987 (i.e., USEPA's NAAQS), levels of respirable particulate (particles of les.s than 10 microns aerodynamic diameter) not exceed 50 pg/m'^ in outdoor air entering a building.

All of the indoor airborne respirable paniculate concentrations measured were less than 50 pg/m\

Carbon Dioxide

Carbon dioxide concentrations measured by Clayton indoors in the building ranged from 420 to 680 parts per million of air (ppm). The outdoor carbon dioxide concentration ranged from 410 to 450 ppm over the 3-day evaluation. The accuracy of the direct-reading in.strumeni used by Clayton i.s ± 50 ppm.

ASHRAE Standard 62-1999 recommends indoor carbon dioxide concentration of not more than 700 ppm above the outdoor carbon dioxide concentration. Based upon the outdoor levels measured over the 3-day evaluation, the recommended upper limit for indoor carbon dioxide concentration.s within the building would be calculated as approximately 1,110 to 1,150 ppm. As such, the interior carbon dioxide concentrations measured by Clayton were less than the ASHRAE Standard 62-1999 upper limit, thereby suggesting an adequate supply of outdoor air to the building.

Carbon dioxide is a product of human respiration and a surrogate for various occupant-generated indoor contaminants. Carbon dioxide does not present a health hazard at these relatively low levels: however, concentrations which exceed the ASHRAE Standard 62-1999 upper limit generally are indicative of insufficient outdoor air ventilation (i.e., outdoor airflows below 15 cubic feet per minute [cfm] per occupant). The OS HA PEL for carbon dioxide exposure is 5.000 ppm as an S-hour time-weighted average (TV/A).

Carbon Monoxide

Carbon monoxide wa.s not detected above 1 ppm at any of the indoor measurement locaiion.s. Likewise, carbon monoxide wa,s consistently measured at I ppm at the Wall Street outdoor sampling location. The accuracy of the direct-reading instrument used by Clayton is ±3 ppm.

3

CITY_21MC100_002388314

NYC-WTC_000390447

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000390447Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000390450

Appendix A shows direct-reading environmental measurements; file references city project codes.

Similar indexed content

Compare copies and versions →