b) All surfaces must be completely dry prior to the start of sampling.
c) Sampling equipment shall be placed at representative locations within
the work area and away from obstructions. The sampling cassette must
be placed on a tripod and not taped to existing surfaces.
d) Air conditioning units where applicable shall be run/operated at least 15
minutes prior to the start of sampling;. The air conditioning units shall
operate continuously throughout the sampling. HVAC systems shall be
in operation during sampling.
e) Forced air equipment (e.g. leaf blowers) may be used only after written
authorization by the occupant or his/her authorized representative. The
project monitor shall advise the occupant or his/her authorized
representative on the advantages and disadvantages regarding the use of
the equipment and obtain the individual’s signature authorizing use. The
authorization shall provide a summary of the advantages and
disadvantages and shall be provided by the USEPA.
Before the start of sampling, forced air equipment (such as a 1
horsepower leaf blower) may be used to direct exhaust air against walls,
ceilings, floor, ledges and other surfaces. When directing the exhaust,
caution shall be taken to minimize disturbance and potential damage to
furnishings and personal belongings.
One 20-inch fan shall be installed pei- 10,000 cubic feet of room space
and run al low speed. The fan shall operate continuously throughout
sampling and shall not be turned off until sampling is completed.
f) For studio apartments 3 samples shall be collected. For 1-bedroom
apartments and above 5 samples shall be collected. Technicians shall
collect a volume of 3000 liters per sample using a flow rate of 10 liters
per minute.
g) Samples must be labeled and accompanied with completed chain of
custody foiTOS before shipping to the designated laboratory.
5. All information must be maintained on a data based software program that is
acceptable to the USEPA. Information in the database shall be updated
every 24 hours . The information shall at a minimum include information on
scheduling, posting of notices, dates of air monitoring and inspections,
results of inspections, sampling results, completion dates, etc.