Mr Bernard P Orlan March 14 2002
Indoor Air Quality Assessment Page 3
H S for Leadership & Public Service fM894) ATCProiectNo 15 19125 0290
Real Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real time environmental measurements
consistmg of one hundred and twenty eight (128) in the school building and twelve (12)
outdoors All fourteen floors of the school were surveyed Field data sheets are found in the
Attachment Readings began at 10 17 AM and concluded after 6 41 P M The results are
described below
Temperature
Indoor dry bulb temperature measurements ranged from 72 4 °F to 79 °F Seventeen (17) indoor
measurement for temperature uere within and one hundred eleven (111) measurements were
above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE
Standard 55 1992 during the heatmg season (wintertime conditions) The outdoor temperature
range was 44 3 °F to 46 8 °F
Relative Humidity
The relative humidity indoors ranged from 30 percent to 41 7 percent All of the indoor
measurements for relative humidity were within the ASHRAE recommended range of 30 to 60
percent for occupant comfort The outdoor relative humidity range was 41 4 to 48 7 percent
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 519 ppm to 1289 ppm All but one of the
indoor measurements for CO2 were below the ASHRAE Standard 62 1999 recommended
maximum concentration of <700 ppm above the background level The outdoor (background)
CO2 concentration was 503 ppm Therefore the maximum acceptable level of CO2 at this
location was 1203 ppm (background level + 700 ppm) The highest readmg (1289 ppm) was
measured in room 1005 at 10 59 AM with 31 occupants Levels above the recommended
maximum do not indicate a health nsk Carbon dioxide measurements are used as an indicator
of available outdoor air The primary source of CO2 indoors is occupant respiration
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 ppm to 3 ppm These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations ranged
from 3 ppm 4 ppm
Respii able Particulates (PM2
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 41 pg/m^ with an
average 15 pg/m^ All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24
hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic
diameter One (1) of the one hundred twenty eight (128) instantaneous indoor readings was
above the USEPA recommended concentration for sensitive individuals such as asthmatic people
and children of 40 pg/m^ The outdoor respirable particulate concentrations ranged from 29
pg/m3 to 94 pg/m3 with an average of 56 pg/m^ Three (3) outdoor measurements were above
the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers
or less in aerodynamic diameter Eleven (11) of the outdoor instantaneous measurements were