Mr Bernard P Orlan March 14 2002
Indoor Air Quality Assessment Page 2
H S for Leadershin & Public Service (M894) ATC Project No 15 19125 0290
The assessment was performed consistent with generally accepted indoor air quality assessment
practices As with all such assessments there were mherent limitations created by constraints of
time operational and work practice variability vanations m mdoor air quality parameters and
sampling and analytical accuracy
The results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times The information presented in this report should be
used by the BOE as a guide to assess the need for further improvements in current indoor air
quality control activities
EVALUATION CRITERIA
Cunently there are no regulatory standards for indoor air quality in non industrial buildings
such as offices and schools For the real time data collected ATC uses the commonly accepted
guidelines cited in the following publications
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62 1999) American Society of
Heating Refrigerating and Air Conditioning Engineers (ASHRAE)
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55 1992)
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993) American
Industnal Hygiene Association (AIHA)
Table 1 lists target guidelines for the parameters that ATC evaluated dunng this investigation
Meeting one some or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times
TABLEI
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
TARGETLEVEL
ORGANIZATION ' ^ y'p'
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2)___________ above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO)____________ USEPA NPAAQS)___________
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2 5) of air (pg/m^) 24 hour average
40 pg/m-^ 24 hour average USEPA - Recommendation for
children / sensitive individuals
Temperature Summer 73 79°F at 50% RH ASHRAE 55
Winter 68 75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE55
Total Volatile
Organic Compounds 1 ppm AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient An Quality Standard
AIHA = American Industnal Hygiene Association